Air Handling Unit Repair for a Midlands University

Date Published:

November 17, 2026

A university in the Midlands had an air handling unit in fault, with an inverter overcurrent error pointing towards a motor problem. Our engineers traced the cause to failing motors and fan bearings, refurbished and rebalanced the components in our workshop, then refitted them with both motors running correctly.

Inside an air handling unit showing the belt-driven fan and two motors before refurbishment

Diagnosing and Refurbishing a Failing AHU: Motors, Fan Bearings and Impeller Balancing

When an air handling unit (AHU) fails, the whole building feels it. At Industrial Refrigeration Services (IRS), we have been keeping air conditioning, refrigeration and ventilation systems running across the UK since 1990. This case study shows how our engineers diagnosed a faulty AHU at a university in the Midlands and refurbished its motors and fan bearings, as part of our wider work for the education sector.

  • Client: A university in the Midlands
  • The problem: AHU in fault, with an overcurrent error showing on the inverter
  • The cause: Failing motor and fan bearings
  • Our solution: Both motors and the fan bearings refurbished in our workshop, with the fan impeller dynamically balanced
  • The outcome: Both motors running correctly, with all work areas left clean and tidy

What Went Wrong with the University’s Air Handling Unit?

We were called to site after reports that one of the university’s AHUs was in fault. When our engineers arrived, the control panel was showing a fault, and the inverter was displaying an overcurrent error. This usually points to the motors working under excessive current, so that is where we began.

Rather than guess, we tested each motor on its own. We removed the drive belts from both motors and dry-ran them independently, which takes the load out of the equation and lets us hear and feel what each motor is doing. Motor 1 ran correctly, with no significant bearing noise. Motor 2 was noisy and vibrating rapidly, which suggested a bearing or motor issue.

A good diagnosis is as much about what you rule out as what you find, so we checked the other common causes too. The filters were in good condition, having been replaced in early July. The manometers were reading correctly, and the supply damper was fully open. Airflow restrictions were not the problem. If you are dealing with a similar symptom, you can also read how we handled a noisy AHU with reduced airflow.

We then refitted the drive belts to Motor 1 only and ran the system up. Once the inverter reached around 30 to 50 Hz, we could hear excessive noise from the fan bearings. That told us the issue was not limited to Motor 2, so we quoted to replace both motors and the fan bearings.

In the meantime, we left the unit running on Motor 1 only. This kept the AHU operational while avoiding excessive torque on the fan, which could have caused further inverter trips.

How Did We Repair the AHU Motors and Fan Bearings?

Our engineers attended site, isolated the unit at the main isolator and removed the covers to reach the fan and motor compartment. They removed the holding-down bolts on both motors, disconnected them electrically and took them out of the AHU. The fan bearings and shaft were removed too, so that everything could be refurbished properly in our workshop.

Doing this work in a workshop rather than in a plant room gives us the space, equipment and control to test and inspect every component. Here is what we did:

  • Dismantled both motors and scope-tested the windings.
  • Cleaned and inspected all parts
  • Fitted two new bearings and two new V-ring seals, then reassembled and tested both motors.
  • Cleaned and polished the main drive shaft and checked its concentricity
  • Supplied two SKF bearings, blocks and all ancillary parts
  • Cleaned and dynamically balanced the fan impeller

That last step matters more than it might seem. An impeller that is out of balance creates vibration, and vibration puts extra strain on bearings. Balancing it before it goes back in helps the new bearings do their job.

We then returned to site to refit the motors and reinstall the fan assembly, adjusting the alignment to suit. We supplied and fitted new timing belts where necessary, reconnected the supply and ran the unit.

The Result

The Operation was confirmed with both motors running correctly, and the fan assembly was left in satisfactory working order. All work areas were left clean and tidy, which is something we take as seriously as the engineering itself. For another example of our work with universities, see our VRF condensing unit replacement at a West Midlands university.

What Did The AHU Refurbishment Include?

The full scope of works for this air handling unit repair was:

  • Remove belts and remove both motors from their base plates
  • Remove main fan flanges to access the fan impeller
  • Dismantle both Plummer block bearings and remove the main drive shaft and fan impeller
  • Take all items back to our workshop facilities.
  • Dismantle both motors and scope test the windings
  • Clean and inspect all parts
  • Fit 2 new bearings and 2 new v-ring seals
  • Reassemble both motors and test
  • Clean and polish the main drive shaft and check shaft concentricity
  • Supply 2 SKF bearings, blocks and all ancillary parts
  • Clean and dynamically balance the fan impeller
  • Reinstall, adjust alignment and fit both motors
  • Supply and fit new timing belts if necessary
  • Connect supply, run and leave the fan assembly in satisfactory working order

Need air handling unit maintenance or repair? Speak to IRS

If your AHU is showing faults, making unusual noise or tripping on overcurrent, our engineers can find the cause and put it right. Regular air handling unit maintenance and AHU servicing can help you spot problems like worn bearings before they become breakdowns. If you are planning new equipment, take a look at our commercial ventilation installations or book a site survey. You can also browse more of our HVAC case studies, or contact our team to talk through your site’s needs.

Air Handling Unit Repair FAQs

What does an overcurrent fault on an AHU inverter mean?

It means the inverter has detected the motor drawing more current than it should. On this job, it pointed us towards a likely bearing or motor issue on Motor 2, which we confirmed by dry-running each motor independently.

How do you diagnose a noisy AHU fan motor?

We remove the drive belts and run each motor on its own, listening for bearing noise and vibration. We also check the filters and manometers to rule out airflow causes, then refit the belts and run the system up to see how the fan bearings behave.

What does an AHU motor and fan bearing refurbishment involve?

We remove the motors, bearings, shaft and impeller, then refurbish them in our workshop. This includes scope testing the windings, fitting new bearings and seals, and dynamically balancing the impeller. We then refit and align everything on site and confirm that both motors run correctly.

What other services does IRS provide?

We specialise in air conditioning, refrigeration, ventilation, energy management and turnkey projects. With more than 150 contracted clients across the UK, we look after a wide range of commercial and industrial sites.

Opened AHU fan bearing showing ball bearings and drive shaft during inspection

Latest News

View More Articles
Service of Air con unit for uk business

Founded in 1990

IRS Ltd (Industrial Refrigeration Services Limited), was founded in 1990 built on a reputation of quality services and cost saving solutions. We are experts in energy management, embracing all aspects of industrial and commercial users of refrigeration, air conditioning and heat exchange systems.

About Us